Brand:Sicon
Description:Basic Information Modular UPS, three phase, online UPS, high frequency, PWM double conversion parallel UPS, N+X redundancy, hot swap modules UPS Power: 150KVA Battery: optional battery pack Back up time: according to load capacity
Origin:China
Model:CMS150/25
MOQ:1Sets
FOB:perCase/Cases1000--6000USD
Port:Xingang
Payment Terms:T/T
Packaging Details:wooden case
Product detail:
Basic Information
Modular UPS, three phase, online UPS, high frequency, PWM double conversion
parallel UPS, N+X redundancy, hot swap modules
UPS Power: 150KVA
Battery: optional battery pack
Back up time: according to load capacity
Overview
CMS UPS units are non-isolated, industrial level, green UPS, adopting advanced modular power protection concept. CMS Modular architecture can scale power as demand grows or as higher levels of availability are required. CMS UPS is industry-leading efficiency, availability, and performance for small, medium, and large data centers and mission critical environments.
Feature
More details :http://www.sicon-emi.com/cms-modular-ups-25-250kva_p23.html
· Rational redundant structure
· UPS module: 25 kVA; System: 150kVA;
· Great performance index
· Overall efficiency ≥ 95%(AC-AC), inverter efficiency ≥ 98%(DC-AC), THDI ≤ 3%, and input PF ≥ 0.99
· N+X module-level redundancy UPS System
· Multi-level decentralized control technology and Master-slave synchronization in sequency control which result in eliminate system failure bottleneck
· Each module automatically even shares the input and output current, all UPS modules share batteries
· Battery management:
· Battery discharge management, auto-transfer between floating and even charging, temperature compensation
· Space-saving high density design, Rack-based for agility and aesthetics
· Monitor Function
· C/S-Oriented Architecture SICON Software which is available to monitor multiple UPS up to 600 sets;
· B/S-Oriented Architecture which is available to check via IE
System model |
CMS-50/10 |
CMS-100/10 |
CMS-150/25 |
CMS-250/25 |
CMS-350/50 |
CMS-500/50 |
CMS-800/50 |
|
Maximum power |
50 kVA |
100kVA |
150 kVA |
250 kVA |
350 kVA |
500kVA |
800KVA |
|
Power module model |
10 kVA |
25KVA |
50KVA |
|||||
Mains Input |
Input mode |
3-phase +N +E, 1-phase +N +E |
||||||
Input voltage |
380V/220V±20%, 400V/230V±20%, 415V/240V±20% |
|||||||
Input frequency |
50Hz±10%, 60Hz±10% |
|||||||
Power woke-in (Sec.) |
60sec |
|||||||
THDI (%) |
<3% |
|||||||
Input PF |
≥0.99 |
|||||||
Bypass Input |
Input voltage |
380V/220V±20%, 400V/230V±20%, 415V/240V±20% |
||||||
Input frequency |
50 Hz, 60 Hz |
|||||||
Range of Frequency Synchro |
50 Hz±4%, 60 Hz±4% |
|||||||
DC Input |
Rated Input voltage |
±384VDC |
||||||
Input voltage tolerance |
±345V~±440V DC |
|||||||
Battery charging |
Charging current limited |
yes |
||||||
Charging ability |
10 hours (2 hours back up) |
|||||||
Stability of charging voltage |
±1% |
|||||||
AC output |
UPS power factor |
0.9 |
||||||
Output voltage |
380V/220V AC, 400V/230V AC, 415V/240V AC |
|||||||
Output frequency |
±4%;±0.2% (battery supply) |
|||||||
Output voltage stability |
±1% |
|||||||
Output voltage recovering time |
<20ms(load 0~100% change) |
|||||||
Overload ability |
Operate 10mins with 125% load |
|||||||
Transfer from mains to battery supply |
0ms |
|||||||
Transfer from bypass to inverter supply |
<1ms |
|||||||
Peak factor |
'3:1 |
|||||||
Waveform distortion |
≤1% ( linear load ), ≤3%( non-linear load ) |
|||||||
Overall efficiency |
≥95% (AC~AC), ≥98% (DC~AC) |
|||||||
Load share precision |
≤5% |
|||||||
Operation environment |
Ambient temperature |
-25℃~60℃ |
||||||
Operating temperature |
-5℃~40℃ |
|||||||
Maximum operation altitude |
≤1500m |
|||||||
Relative humidity |
≤95% non-cadency |
|||||||
Protection degree |
IP30 |
|||||||
Cooling |
Air cooling |
|||||||
Applicable safety standards |
EN62040-1-1:2003 IEC60950-1:2001 |
|||||||
Electromagnetic compatibility |
EN62040-2:2006 |
|||||||
Acoustic noise |
≤55DB |
|||||||
Others |
Cabinet |
Standard 19 inch cabinet |
||||||
Monitor management system |
UPSupervisor |
|||||||
Interface |
RS232, RS485 and 8 try contact, TCP/IP adapter, SNMP(optional) |
|||||||
Display |
Touch LCD/LED Screen |
|||||||
Weight(kg) |
150 |
200 |
200 |
260 |
400 |
500 |
700 |
· Standard configuration
Application
Small server room, network, bank, security, transportation, broadcast&TV network, HealthCare, Communication, Finance.
Contact Sicon:
Corporate URL: www.sicon-emi.com
Email:enquiry@scupower.com
Tel: +86 311 85903762