Brand:aa
Product detail:
CE Certificate R407C,R134A,R22,High Quality Screw Chiller,Air Cooled Water Chiller,Industrial Chiller with Bitzer,Refcomp,Hanbell Screw Compressor
FEATURES:
1.Twin screw compressors of world famous brand is adopted, with high efficiency, low noise level, less wearing and long operation time.
2.The unit is of high performance as they are made of the condensers and evaporators of grooved copper pipes, and high quality components, by specialized process.
3.The unit is easy to operate, and friendly interfaced, as they adopt leading brand PLC, 64K color touch screen and other control elements.
4.The energy saving for Multi-capacity regulation resulted in cost cut down for operation and maintenance.
Kinds of models of Air Cooled Water Chillers:
a.Single Compressor Models
MODEL LTLF- | 30AS | 40AS | 50AS | 60AS | 70AS | 80AS | 90AS | 100AS | 110AS | 120AS | 130AS | 140AS | |
Cooling Capacity | KW | 87 | 117 | 155 | 200 | 224 | 278 | 305 | 330 | 363 | 430 | 456 | 500 |
103kcal/hr | 75 | 101 | 133 | 172 | 193 | 239 | 262 | 284 | 312 | 370 | 392 | 430 | |
Compressor | Power(kW) | 28.4 | 37.4 | 46.9 | 62.7 | 68.3 | 80.8 | 89 | 97.1 | 108 | 125.4 | 132.4 | 143.4 |
Current(A) | 47.8 | 62.9 | 78.9 | 105.3 | 114.7 | 135.9 | 149.6 | 163.2 | 181.5 | 210.8 | 222.5 | 241.1 | |
Capaty Regul | 0-33-66-100%(33% for start) | 0-50-75-100%(25% for start) | |||||||||||
Power(kW) | 31.5 | 40.7 | 51.6 | 69.3 | 74.9 | 90.2 | 98.4 | 106.5 | 119.2 | 137.9 | 145 | 157 | |
Current(A) | 57.4 | 74.3 | 93.3 | 128.1 | 137.5 | 164.7 | 178.4 | 192 | 213.5 | 249.2 | 260.9 | 281.1 | |
Refrigerant | Type | R22 | |||||||||||
Control | Thermal expension valve | ||||||||||||
Cooling fan | Quantity | 2 | 3 | 3 | 6 | 6 | 6 | 6 | 6 | 8 | 8 | 8 | 10 |
Single motor power | 1.56 | 1.1 | 1.56 | 1.1 | 1.1 | 1.56 | 1.56 | 1.56 | 1.4 | 1.56 | 1.56 | 1.4 | |
Current(A) | 4.8 | 3.8 | 4.8 | 3.8 | 3.8 | 4.8 | 4.8 | 4.8 | 4 | 4.8 | 4.8 | 4 | |
Evaporator | water pipe connection | DN65Flg | DN80Flg | DN100Flg | DN125Flg | ||||||||
Water flow(m³/h) | 15 | 20 | 27 | 34 | 39 | 48 | 52 | 57 | 62 | 74 | 78 | 86 | |
P drop(KPa) | 37 | 37 | 39 | 42 | 42 | 45 | 45 | 46 | 48 | 48 | 49 | 49 |
b.Double Compressors Models
MODEL LTLF- | 60AD | 80AD | 100AD | 120AD | 140AD | 160AD | 180AD | 200AD | 220AD | 240AD | 260AD | 280AD | |
Cooling Capacity | KW | 174 | 234 | 310 | 400 | 448 | 556 | 610 | 660 | 726 | 860 | 912 | 1000 |
103kcal/hr | 150 | 201.2 | 266.6 | 344 | 385.3 | 478.2 | 524.6 | 567.6 | 624.4 | 740 | 784.3 | 860 | |
Compressor | Power(kW) | 56.8 | 74.8 | 93.8 | 125.4 | 136.6 | 161.6 | 178 | 194.2 | 216 | 250.8 | 264.8 | 286.8 |
Current(A) | 95.6 | 125.8 | 157.8 | 210.6 | 229.4 | 271.8 | 299.2 | 326.4 | 363 | 421.6 | 445 | 482.2 | |
Capaty Regul | 0-16.5…100%(16.5% for start) | 0-12.5…...100%(12.5% for start) | |||||||||||
Power(kW) | 61 | 84.2 | 103.2 | 137.9 | 150.6 | 180.3 | 196.7 | 212.9 | 238.4 | 275.8 | 290 | 315 | |
Current(A) | 109.4 | 154.6 | 186.6 | 249 | 277.4 | 329.4 | 356.8 | 384 | 427 | 498.4 | 521.8 | 562.2 | |
Refrigerant | Type | R22 | |||||||||||
Control | Thermal expension valve | ||||||||||||
Cooling fan | Quantity | 6 | 6 | 6 | 8 | 10 | 12 | 12 | 12 | 16 | 16 | 16 | 20 |
Single motor power | 0.7 | 1.56 | 1.56 | 1.56 | 1.4 | 1.56 | 1.56 | 1.56 | 1.4 | 1.56 | 1.56 | 1.4 | |
Current(A) | 2.3 | 4.8 | 4.8 | 4.8 | 4.8 | 4.8 | 4.8 | 4.8 | 4 | 4.8 | 4.8 | 4 | |
Evaporator | water pipe connection | DN80Flg | DN100Flg | DN125Flg | DN150Flg | ||||||||
Water flow(m³/h) | 30 | 40 | 53 | 69 | 77 | 96 | 105 | 114 | 125 | 148 | 157 | 172 | |
P drop(KPa) | 50 | 50 | 51 | 52 | 53 | 53 | 58 | 58 | 65 | 66 | 70 | 70 |
Remark:1.Colling Condition:Cold water in/out 12/7°C; Environmental 35°C;
2.Power supply: 3P-380V-50HZ;with voltage allowance ±10%,voltage dif between the phase lines±2%;
3.The data above is for R22, contact us if that for R134a,R407c and other refrigerant need;
4.There may be Changes for improvement without notice, confirm always before your order.
Certificate of Products