0.6/1(1.2) kV Twisted cable
1). Standard: IEC60502, NF C33-209, GB 12527-90
2). Rated voltage: 0.6/1kV
3). Specification:
* Aluminium conductor(AAC) as phase conductor;
* Aluminium alloy conductor(AAAC) or ACSR as Messenger (Neutral) core;
* XLPE or HDPE or PVC insulation.
4). Application:
The cable as a new-type aerial cable is used for transmitting electric power overhead, extensively used in rebuilding of urban and forest region electrified wire netting. It improves the safety and reliance of electrified wire netting.
Technical Characteristics Based on Standard NF C 33-209
Designation | Conductor | Average thickness of insulation (XLPE) | Insulated conductor | ||||||
Conductor type | Nominal area | Number of wires | Max. D.C. resistance at 20oC | Diameter of conductor | Min. breaking load | Overall diameter | |||
Min. | Max. | Min. | Max. | ||||||
mm2 | No. | Ω/km | mm | mm | kN | mm | mm | mm | |
Phase or neutral non- messenger or street lighting | 16 | 7 | 1.91 | 4.6 | 5.1 | 1.9 | 1.2 | 7.0 | 7.8 |
25 | 7 | 1.20 | 5.8 | 6.3 | 3.0 | 1.4 | 8.6 | 9.4 | |
35 | 7 | 0.868 | 6.8 | 7.3 | - | 1.6 | 10.0 | 10.9 | |
50 | 7 | 0.641 | 7.9 | 8.4 | - | 1.6 | 11.1 | 12.0 | |
70 | 12 | 0.443 | 9.7 | 10.2 | - | 1.8 | 13.3 | 14.2 | |
95 | 19 | 0.320 | 11.0 | 12.0 | - | 1.8 | 14.6 | 15.7 | |
120 | 19 | 0.253 | 12.0 | 13.1 | - | 1.8 | 15.6 | 16.7 | |
150 | 19 | 0.206 | 13.9 | 15.0 | - | 1.7 | 17.3 | 18.6 | |
Neutral messenger | 54.6 | 7 | 0.63 | 9.2 | 9.6 | 16.6 | 1.6 | 12.3 | 13.0 |
70 | 7 | 0.50 | 10.0 | 10.2 | 20.5 | 1.5 | 12.9 | 13.6 | |
95 | 19 | 0.343 | 12.2 | 12.9 | 27.5 | 1.6 | 15.3 | 16.3 |