Outback FlexPower Two FP2-12 Power Center
Model | Part Number | Output Watts | Input Current | Voltage DC/AC | Type | Inverter |
FlexPower Two FP2-12 | 03304133 | 7,000 | 60 Amps | 24 / 120 or 240 | Off-Grid | 2 - VFX3524 |
Outback FlexPower Two Power Center Specifications
FP2-10 | 7.2 kW FLEXpower TWO, Pre-wired AC and DC boxes with 120VAC Bypass , two 175ADC breakers, two VFX3648 inverter/chargers, MATE2, HUB10, RTS, X-240 and surge protector for 120V/240V 60Hz applications |
FP2-12 | 7 kW FLEXpower TWO, Pre-wired AC and DC boxes with 120VAC Bypass, two 250ADC breakers, two VFX3524 inverter/chargers, MATE2, HUB10, RTS, X-240 and surge protector for 120V/240V 60Hz applications |
FP2-22 | 6 kW FLEXpower TWO, Pre-wired AC and DC boxes with 230VAC Bypass, two 175ADC breakers, two VFX3048E inverter/chargers, MATE2, HUB10 and RTS for 230V 50Hz applications |
FP2-24 | 6 kW FLEXpower TWO, Pre-wired AC and DC boxes with 230VAC Bypass, two 250ADC breakers, two VFX3024E inverter/chargers, MATE2, HUB10 and RTS for 230V 50Hz applications |
FP2-28 | 7 kW FLEXpower TWO, Pre-wired AC and DC boxes with 120VAC Bypass, two 250ADC breakers, two GVFX3524 inverter/chargers, MATE2, HUB10, RTS, and surge protector for 120V/240V 60Hz applications |
FP2-29 | 7.2 kW FLEXpower TWO, Pre-wired AC and DC boxes with 120VAC Bypass, two 175ADC breakers, two GVFX3648 inverter/chargers, MATE2, HUB10, RTS, and surge protector for 120V/240V 60Hz applications |
FP2-30 | 6 kW FLEXpower TWO, Pre-wired AC and DC boxes with 120VAC Bypass, two 175ADC breakers, two GTFX3048-HI inverter/chargers, MATE2, HUB10, RTS, and surge protector for 120V/240V 60Hz applications |
FP2-31 | 6 kW FLEXpower TWO, Pre-wired AC and DC boxes with 120VAC Bypass, two 175ADC breakers, two FX3048T inverter/chargers, MATE2, HUB10, RTS, X-240 and surge protector for 120V/240V 60Hz applications |
FP2-32 | 5 kW FLEXpower TWO, Pre-wired AC and DC boxes with 120VAC Bypass, two 250ADC breakers, two FX2524T inverter/chargers, MATE2, HUB10, RTS, X-240 and surge protector for 120V/240V 60Hz applications |
FP2-33 | 5 kW FLEXpower TWO, Pre-wired AC and DC boxes with 120VAC Bypass, two 250ADC breakers, two GTFX2524-HI inverter/chargers, MATE2, HUB10, RTS, and surge protector for 120V/240V 60Hz applications |
Weight | Unit 232 lbs (105 kgs) Shipping 282 lbs (127 kgs) |
(H x W x L) | Unit 20.25 x 46.5 x 13 (51.4 x 118.1 x 33 cm) Shipping 21.5 x 47.5 x 20.5” (54.6 x 120.7 x 52.1 cm) |
Outback Flexmax 80 / 60 Charge Controller Specifications |
FLEXmax 80 Specifications | FLEXmax 60 Specifications | |
---|---|---|
Nominal Battery Voltages | 12, 24, 36, 48, or 60 VDC (Single model - selectable via field programming at start-up) | 12, 24, 36, 48, or 60 VDC (Single model - selectable via field programming at start-up) |
Maximum Output Current | 80 amps @ 104° F (40°C) with adjustable current limit | 60 amps @ 104° F (40°C) with adjustable current limit |
Maximum Solar Array STC Nameplate | 12 VDC systems 1250 Watts / 24 VDC systems 2500 Watts / 48 VDC systems 5000 Watts / 60 VDC systems 6250 Watts | 12 VDC systems 900 Watts / 24 VDC systems 1800 Watts / 48 VDC systems 3600 Watts / 60 VDC Systems 4500 Watts |
NEC Recommended Solar Array STC Nameplate | 12 VDC systems 1000 Watts / 24 VDC systems 2000 Watts / 48 VDC systems 4000 Watts / 60 VDC Systems 5000 Watts | 12 VDC systems 750 Watts / 24 VDC systems 1500 Watts / 48 VDC systems 3000 Watts / 60 VDC Systems 3750 Watts |
PV Open Circuit Voltage (VOC) | 150 VDC absolute maximum coldest conditions / 145 VDC start-up and operating maximum | 150 VDC absolute maximum coldest conditions / 145 VDC start-up and operating maximum |
Standby Power Consumption | Less than 1 Watt typical | Less than 1 Watt typical |
Power Conversion Efficiency | 97.5% @ 80 Amps in a 48 VDC System - Typical | 98.1% @ 60 Amps in at 48 VDC System voltage - Typical |
Charging Regulation | Five Stages: Bulk, Absorption, Float, Silent and Equalization | Five Stages: Bulk, Absorption, Float, Silent and Equalization |
Voltage Regulation Set points | 10 to 80 VDC user adjustable with password protection | 10 to 80 VDC user adjustable with password protection |
Equalization Charging | Programmable Voltage Set point and Duration - Automatic Termination when completed | Programmable Voltage Set point and Duration - Automatic Termination when completed |
Battery Temperature Compensation | Automatic with optional RTS installed / 5.0 mV per °C per 2V battery cell | Automatic with optional RTS installed / 5.0 mV per °C per 2V battery cell |
Voltage Step-Down Capability | Can charge a lower voltage battery from a higher voltage PV array - Max 150 VDC input | Can charge a lower voltage battery from a higher voltage PV array - Max 150 VDC input |
Programmable Auxiliary Control Output | 12 VDC output signal which can be programmed for different control applications (Maximum of 0.2 amps DC) | 12 VDC output signal which can be programmed for different control applications (Maximum of 0.2 amps DC) |
Status Display | 3.1" (8 cm) backlit LCD screen - 4 lines with 80 alphanumeric characters total | 3.1" (8 cm) backlit LCD screen - 4 lines with 80 alphanumeric characters total |
Remote Display and Controller | Optional Mate or Mate2 with RS232 Serial Communications Port | Optional Mate or Mate2 with RS232 Serial Communications Port |
Network Cabling | Proprietary network system using RJ 45 Modular Connectors with CAT 5e Cable (8 wires) | Proprietary network system using RJ 45 Modular Connectors with CAT 5e Cable (8 wires) |
Data Logging | Last 128 days of Operation - Amp Hours, Watt Hours, Time in Float , Peak Watts, Amps, Solar Array Voltage, Max Battery Voltage Min Battery Voltage and Absorb for each day along with total Accumulated Amp Hours, and kW Hours of production | Last 128 days of Operation - Amp Hours, Watt Hours, Time in Float , Peak Watts, Amps, Solar Array Voltage, Max Battery Voltage Min Battery Voltage and Absorb for each day along with total Accumulated Amp Hours, and kW Hours of production |
Hydro Turbine Applications | Consult factory for approved Turbines | Consult factory for approved Turbines |
Positive Ground Applications | Requires two Pole Breakers for switching both positive and Negative Conductors on both Solar Array and Battery Connections (HUB-4 and HUB-10 can not be used for use in positive ground applications) | Requires two Pole Breakers for switching both positive and Negative Conductors on both Solar Array and Battery Connections (HUB-4 and HUB-10 can not be used for use in positive ground applications) |
Operating Temperature Range | Minimum -40° to maximum 60° C (Power capacity of the controller is automatically derated when operated above 40° C) | Minimum -40° to maximum 60° C (Power capacity of the controller is automatically derated when operated above 40° C) |
Environmental Rating | Indoor Type 1 | Indoor Type 1 |
Conduit Knockouts | One 1" (35mm)on the back; One 1" (35mm) on the left side; Two 1" (35mm) on the bottom | One 1" (35mm)on the back; One 1" (35mm) on the left side; Two 1" (35mm) on the bottom |
Warranty | Standard 5 year / Available 10 Year | Standard 5 year / Available 10 Year |
Weight - Unit | 12.20 lbs (5.56 kg) | 11.65 lbs (5.3 kg) |
- Shipping | 15.75 lbs (7.10 kg) | 14.55 lbs (6.4 kg) |
Dimensions - Unit | 16.25" x 5.75" x 4" (41.3 x 14 x 10 cm) - (H x W x D) | 13.5 x 5.75 x 4" (40 x 14 x 10 cm) |
- Shipping | 21" x 10.5" x 9.75" (53 x 27 x 25 cm) | 18 x 11 x 8" (46 x 30 x 20 cm) |
Options | Remote Temperature Sensor (RTS), HUB 4, HUB 10, MATE, MATE 2 | Remote Temperature Sensor (RTS), HUB 4, HUB 10, MATE, MATE 2 |
Menu Languages | English & Spanish | English & Spanish |