SMA / MidNite Solar AC Coupled Kit
Model | Item Code | # Solar Panels | Pass-Through Rating | Peak AC Surge | Battery Storage | Power Supply | No Load Draw |
Sunny Island MNSMA1 AC | BP28MNSMA1AC | None | 56 Amps | 11,000W | 12,480 Watts AGM | Solar / Grid | 25 Watts |
<
Technical Data | Sunny Island 4548-US | Sunny Island 6048-US |
AC output (loads)))) | ||
Rated grid voltage / AC voltage range | 120 V (105 V – 132 V) | 120 V (105 V – 132 V) |
Rated frequency / frequency range (adjustable) | 60 Hz (55 Hz - 65 Hz) | 60 Hz (55 Hz - 65 Hz) |
AC power at 25 °C / 40 °C for 3 hours | 5000 W / 4000 W | 6000 W / 5000 W |
Rated power (@U(nom), f(nom) / 25 °C / cos f = 1) | 4500 W | 5750 W |
AC output power at 3 s | 25 °C (77 °F) for 30 min / 1 min / 5300 W / 8400 W / 11000 W | 7000 W / 8400 W / 11000 W |
Rated current / Max. output current (peak) | 37.5 A / 180 A for approx. 60 ms | 48 A / 180 A for approx. 60 ms |
Total harmonic factor output voltage / power factor at rated power | 3% / -1 ... +1 | 3% / -1 ... +1 |
AC input (PV array or grid)) | ||
Rated input voltage / AC input voltage range | 120 V (80 V – 150 V) | 120 V (80 V – 150 V) |
Rated input frequency / allowable input frequency range | 60 Hz / 54 Hz ... 66 Hz | 60 Hz / 54 Hz ... 66 Hz |
Max. AC input current / adjustable | 56 A / 0 A ... 56 A | 56 A / 0 A ... 56 A |
Max. AC input power | 6.7 kW | 6.7 kW |
Battery DC inputt | ||
Rated input voltage / DC voltage range | 48 V / 41 V - 63 V | 48 V / 41 V - 63 V |
Max. battery charging current / DC rated charging current | 100 A / 85 A | 130 A / 110 A |
Battery type / battery capacity range | Lead, NiCd / 100 Ah - 10000 Ah | Lead, NiCd / 100 Ah - 10000 Ah |
Charge control | IUoU charge procedure with automatic full charge and equalization charge | IUoU charge procedure with automatic full charge and equalization charge |
Efficiency / self-consumptionn | ||
Max. efficiency / CEC efficiency | 96% / 94.5% | 96% / 94% |
Self consumption with no load / standby | 25 W / 4 W | 25 W / 4 W |
Protective Devicess | ||
DC reverse polarity protection / DC fuse | yes/yes | yes/yes |
AC short-circuit / AC overload | yes/yes | yes/yes |
Overtemperature / battery deep discharge | yes/yes | yes/yes |
General dataa | ||
Dimensions (W/H/D) | 467/612/235 mm (18.4/24.1/9.3 inch) | 467/612/235 mm (18.4/24.1/9.3 inch |
Weight | 63 kg /139 lb | 63 kg /139 lb |
Operating temperature range | –25 °C ... +60 °C (–13 ° F ... +122 °F) | –25 °C ... +60 °C (–13 ° F ... +122 °F) |
Features / functionn | ||
Operation and display / multi-function relay | Internal/2 | Internal/2 |
Degree of protection (according to IEC 60529) | internal assembly (NEMA 1) | internal assembly (NEMA 1) |
Three-phase systems/parallel connection | yes/yes | yes/yes |
Integrated bypass/multicluster operation | no/yes | no/yes |
State of charge calculation/full charge / equalization charge | yes/yes/yes | yes/yes/yes |
Integrated soft start/generator support | yes/yes | yes/yes |
Battery temperature sensor/data cable | yes/yes | yes/yes |
Warranty: 5/10/15/20 years | yes/opt./opt./opt./opt. | yes/opt./opt./opt./opt. |
Certificates and approvals | www.SMA-Solar.com | www.SMA-Solar.com |
Accessories | ||
Battery cables/battery fuse | opt./opt. | opt./opt. |
Interfaces (RS485/Multicluster PB) | opt./opt. | opt./opt. |
Extended generator start "GenMan" | opt. | opt. |
Load-shedding contactors/external battery current measurement | opt./opt. | opt./opt. |
Type designation | SI4548-US-10 | SI6048-US-10 |