1). ABC Cable use the following conductors:
All Aluminum Conductors AAC | ASTM B 231 |
All Aluminum Conductors AAC | BS 215 Part 1 |
All Aluminum Conductors AAC | BS EN 50182 |
All Aluminum Conductors AAC | IEC 61089 |
All Aluminum Conductors AAC | DIN 48201 |
Aluminum Conductor Steel Reinforce ACSR | ASTM B 232 |
Aluminum Conductor Steel Reinforce ACSR | BS 215 Part 2 |
Aluminum Conductor Steel Reinforce ACSR | BS EN 50182 |
Aluminum Conductor Steel Reinforce ACSR | IEC 61089 |
Aluminum Conductor Steel Reinforce ACSR | DIN 48204 |
Bare All Aluminum Alloy Conductor (Bare AAAC) | ASTM B 399 |
Bare All Aluminum Alloy Conductor (Bare AAAC) | BS 3242 |
Bare All Aluminum Alloy Conductor (Bare AAAC) | DIN 48201 |
Bare All Aluminum Alloy Conductor (Bare AAAC) | AS 1531 Part 2 |
Aerial Bundle Cable (ABC) |
2. Characters
a. Max operating temperature: XLPE insulation 90°C,High-density PE insulation 75°C,PVC insulation 70°C.
b. Installing temperature of cable should not be below -20°C.
c. Max short-circuit temperature: No more than5 Sec: XLPE insulation 250°C,High-density PE insulation 150° C,PVC insulation 130°C.
d. Permissible Bending radius of cable: Should be not less than 20(d+D)±5mm. Note: D is overall diameter of cable; d is diameter of conductor.
e. Conductor: Aluminum, Copper, AAC, ACSR, and AAAC etc.
f. Insulation: XLPE or PVC or PE
g. Standard: According to IEC, also can do by standard of ASTM, BS, GB, DIN and AS/NZS or other standards.
h. Rated Voltage:0.6/1KV 6.35/11kv