Product Name: under current protection relay (GTT-822)
A. Scope of Application:
It mainly applies to 110 kV and the following various voltage levels two / three coil transformer protection
device.
B.Function and Characteristics :
Classify | Function Selection |
Protection Function |
Two section over current |
Over current speed protection | |
over load protection | |
High voltage zero sequence over current protection | |
Low voltage Zero sequence over current protection | |
Non power capacity protection | |
Low voltage protection | |
Zero sequence voltage protection | |
Operation Cicuit |
Power completely independent containing anti adjustable locking function operation circuit |
Control circuit abnormal alarm | |
Control Function |
remote signal value collection, accident remote signal |
Circuit breaker remote control deciliter | |
IA,IC,P,Q,Uab,Ubc,Uca,f etc telemetry | |
Switch accident statistics division | |
The event SOE alarm | |
Fault recorder Function | |
Time Hack |
GPS and network time synchronization |
Communication | Ethernet,RS232/485 communication interface |
Protection relay Front view
Protection relay Back view
C.Main Features:
a. 4U standard aluminum chassis, combination of plug-in structure, after the plug case, each
functional module design alone, electricity are completely separated, strong
anti-interference ability, convenient field maintenance;
b. CPU intelligent card design, open into the open plug-ins to achieve real-time complete
self-test; can be detected in each relay coil;
c. Plug-in based on CANBUS bus links between, reduce the connection between the
connector plug, bad real time detection;
d. Double 32 computer systems, the redundant system; protection function using the Dezhou
Instrument Company produced the 32 bits floating-point DSP processor, program and data
in the chip operation; operation speed, high reliability;
e. Man-machine interface, network communication and other management functions by
Philips Company produced 32 ARM MCU, speed, on-chip memory capacity big, strong
ability of network interface;
f. 16 AD sampling, high measuring precision; weekly wave 48 sampling points, harmonic
processing capability;
g. Protection module using computer assisted graphical interface design is convenient for the
two series of products development and functional modifications, flexible, efficient
engineering design;
h. Complete the circuit breaker control circuit is provided with a remote control, jump,
closing, spring without stored energy blocking close function etc;
i. Use 192*64 monochrome graphic LCD, Chinese menu interface; the flexibility to choose
double Ethernet and double 485 interface;
j. Can save at least 500 report recent incidents and operation report;
k. User management module using real-time multitask operating system, network interface,
tasks such as real-time;
l . Can store 10 sets of protection setting value, double value zone self-test and mutual
combination, setting change safely and convenient.
m. Based on electric power industry standard DL / T667-1999 (IEC 60870-5-103) standard
communication protocol, and convenient with microcomputer monitoring or protect
management computer network communication.
D.Rated Data:
Rated AC voltage: 220V (110V orders indicate) allowable deviation +15%,-20%
a. Rated AC data: phase voltage 100√ 3 V
Zero-sequence voltage 100V
AC current 5A (1A orders indicate)
Rated frequency 50Hz (60Hz orders indicate)
b. Thermal Stability:
AC voltage circuit: long time operation 1.4Un
AC current circuit: long time operation 2In
10s 20In
1s 40In
Our products advantages
Function Introduction
The main function includes protection, data collection, controlling, communication,
debugging and security.
The device is applied to sub computer workstation function designed.
It can not only be used separately as digital protection device, but also form systems
with different structures.
Protection Principle
1)Over-current section I Protection
Over-current section I principle diagram
2) Over-current section II Protection
The principle of signal similar with Picture
3) Over-current section III Protection (Inverse time limited)
4)Overload
Overload Schematic Diagram
5) Non-electricity Protection
6) Zero-sequence current Protection
Zero-sequence current Schematic Diagram
7) Low Voltage Protection
Low voltage protection principle diagram
8) TV Disconnection Test
9) Control Circuit Abnormity Alarm
10) Device Fault Alarm
11) Telemetry, Remote Signal, Remote Control Function
12) Wave Recorder
13) GPS Time Synchronization
Factory pictures