1. Cooling capacity for water cooled chiller with two sets of compressor: 70-570Tons
2. Superior Performance: international advanced semi-closed screw compressor; several refrigerant circuits insure no stop when one circuit needs maintenance; low noise; efficient heat transfer;
3. Easy Installation: compact structure, take up limited space; refrigerant has been filled in the chiller so as to save time and expenses.
4. Low Cost for Operation and Maintenance;
5. Comprehensive Security Protection: high and low pressure protection, electric motor protection, safety valve protection, all the above protections ensure the unit safe and stable in operation.
6. Intelligent controller, english touch screen.
7. Energy control: 25%-50%-75%-100% four step levels energy adjustment .
8. Optional:Air cooled chiller, low temperature chiller ,industrial water chiller, water chiller , water cooling unit ,sml series chiller , cooler.
Technical parameters of water cooled twin screw chillers | |||
Model | MG-400WS | ||
Nominal cooling capacity | kcal/h | 1,100,600 | |
kw | 1280 | ||
Input power | kw | 226.6 | |
Running current | A | 380.8 | |
Chilled fluid flow | M3/h | 220.1 | |
Cooling water flow | M3/h | 259.1 | |
Power supply | 3PH-380V-50HZ | ||
Refrigeration oil | Type | SUNISO 4GS | |
Charge | L | 12*2 | |
Refrigerant | Type | R22/R134a/407c | |
Charge | Kg | 94*2 | |
Type of control | Thermostatic expansion valve | ||
Compressor | Type | Semi-hermetic screw | |
Quantity | 2 sets | ||
start-up mode | Y | ||
power | Kw | 113.3*2 | |
Capacity control | % | 0~100( 8 level Capacity control) | |
Evaporator | type | Shell and tube | |
Inlet and outlet pipe diameter | inch | PT5" | |
Condenser | Type | Shell and tube | |
Inlet and outlet pipe diameter | inch | PT4"*2 | |
Dimension | Length | mm | 3200 |
Width | mm | 1200 | |
Height | mm | 1760 | |
Net weight | Kg | 5370 | |
Safety protection | compressor over temperature, unit overload, high and low pressure, flow switch, phase sequence, phase-missing, antifreezing | ||
Note: 1.Nominal cooling capacity is according to: Inlet chilled fluid temperature: 7°C Outlet chilled fluid temperature: 12°C Inlet cooling water temperature: 30°C Outlet cooling water temperature: 35°C We reserve the right to modify the above dimension or parameter without further notice. And we can manufacture diferent type chillers as per your need. | |||