Technical parameters:
1. Normal line voltage <1000V
2. Rated current ≤ 2000A
3. Dielectric strength: winding-earth 3000VAC/50Hz/60s no arcing or breakdown
4. Insulation resistance: winding-earth, cross-core screw rob - earth 500VDC, insulation resistance value ≥100MΩ
5. Noise level < 65dB (The testing point's horizontal distance from transformer should be 1 metre.)
6, Protection degree: IP00
7. Insulation class: H
8. Product standards: IEC289:1987 Reactors
GBI0229-88 Reactor (EQV IEC289:1987)
Application environment and conditions:
1, The altitude is not more than 1000 meters and if more than 1000 meters, derating is required.
2, Running temperature: -5 ℃-40 ℃, relative humidity is less than 90%.
3, Without harmful gas, inflammable, explosive and conductive dust around.